Size equipment grounding conductors (EGC) and grounding electrode conductors (GEC) based on NEC 250.122 and 250.66.
| OCPD Size (Amps) | Copper EGC Size | Aluminum EGC Size |
|---|---|---|
| 15A | 14 AWG | 12 AWG |
| 20A | 12 AWG | 10 AWG |
| 30A / 40A / 60A | 10 AWG | 8 AWG |
| 100A | 8 AWG | 6 AWG |
| 200A | 6 AWG | 4 AWG |
| 300A | 4 AWG | 2 AWG |
| Copper Service Conductor | Copper GEC Size | Aluminum GEC Size |
|---|---|---|
| 2 AWG or smaller | 8 AWG | 6 AWG |
| 1 AWG or 1/0 AWG | 6 AWG | 4 AWG |
| 2/0 AWG or 3/0 AWG | 4 AWG | 2 AWG |
| 4/0 AWG to 350 kcmil | 2 AWG | 1/0 AWG |
Grounding and bonding are the cornerstones of electrical safety in solar PV systems. A properly sized equipment grounding conductor (EGC) provides a safe, low-impedance path for fault currents to return to the source, tripping the overcurrent protective device (breaker or fuse) and clearing the fault. In rooftop solar arrays, metal racking, PV module frames, and metal conduits are all exposed to the elements and potential physical damage. If a hot conductor faults to a metal rack that is poorly grounded or lacks a properly sized EGC, the entire racking system can become energized, posing a fatal shock hazard.
NEC Article 250 governs grounding and bonding requirements. EGC sizing is dictated by Table 250.122, while Grounding Electrode Conductor (GEC) sizing is governed by Table 250.66. Grounding electrode conductors connect the main electrical panel (or solar service disconnect) to the earth via a ground rod, water pipe, or Ufer ground, protecting the entire system from lightning surges and high-voltage line spikes.
One critical rule solar designers often overlook is NEC 250.122(B). If the ungrounded circuit conductors are upsized to compensate for voltage drop on long conduit runs (common in ground mounts or remote arrays), the equipment grounding conductor must also be upsized proportionally. Failing to verify grounding sizes leads to immediate inspection failures and delays solar permission-to-operate (PTO).
A solar contractor is installing a commercial solar subpanel. The subpanel is fed from a main distribution board with a 200A circuit breaker. The contractor needs to size the copper Equipment Grounding Conductor (EGC) that will be routed inside the conduit feeding the subpanel.
Inputs: Grounding type = EGC, OCPD Rating = 200 Amps, Ground conductor material = Copper.
Calculation: Using NEC Table 250.122, we find the row corresponding to a 200 Amp overcurrent device rating. For a 200A OCPD, the minimum size copper equipment grounding conductor required is #6 AWG. (If aluminum was used, the minimum size would be #4 AWG).
Result: The installer must run a #6 AWG copper EGC inside the conduit. If the distance between the main panel and the solar subpanel was long and required upsizing the phase conductors to #3/0 AWG instead of the standard #2/0 AWG to combat voltage drop, the #6 AWG EGC would also have to be upsized proportionally using the circular mil calculation method under NEC 250.122(B).
An Equipment Grounding Conductor (EGC) connects non-current-carrying metal parts of equipment (like PV module frames and racking) to the system grounded conductor or grounding electrode at the service equipment. It is sized based on the overcurrent protective device (OCPD) rating using NEC Table 250.122. A Grounding Electrode Conductor (GEC) connects the system grounded conductor or service equipment to a grounding electrode (like a ground rod). It is sized based on the service entrance conductor size using NEC Table 250.66.
NEC Table 250.122 dictates that EGC sizes are directly proportional to the size of the circuit breaker or fuse protecting the circuit. If a circuit breaker is upsized (for example, to prevent nuisance tripping or due to voltage drop calculations requiring larger ungrounded conductors), the EGC must also be upsized proportionally according to NEC 250.122(B).
Yes, aluminum grounding conductors are permitted by the NEC, but they must comply with specific installation rules. Per NEC 250.64(A), bare or covered aluminum conductors cannot be used where in direct contact with masonry or earth, or where subject to corrosive conditions. When used outdoors, aluminum GECs must not be terminated within 18 inches of the earth, making copper the default preference for many residential installers.
Stop sizing grounding conductors manually. Automate electrical compliance, PV design generation, and plan checks in one platform.
Automate your full permit pipeline with SolaricyGrounding Conductor Sizing Report
Project: N/A
Designer: N/A
Date:
| Grounding Type: | Equipment Grounding Conductor (EGC) |
| Conductor Material: | Copper (Cu) |
| Breaker Rating (OCPD): | 20 Amps |
| Recommended Grounding Size: | AWG 12 |
| NEC Table Reference: | Table 250.122 |
This report is for informational and educational sizing purposes. Calculations comply with standard engineering formulas and NEC guidelines.
Generated by Solaricy — solaricy.com/tools/grounding-conductor