Wire Sizer & Voltage Drop

Size conductors and calculate voltage drop according to NEC guidelines.

Conductor Specifications

PDF Report Branding (White-Label)

Wire Recommendation

Optimal Size (75°C Conductor) AWG 10 Copper (Cu) Conductor
Voltage Drop % 1.8%
Voltage Drop (V) 2.1 V
Actual Voltage at Load 117.9 V
75°C Ampacity Rating 35A
Conductor Resistance 1.21 Ω / 1k ft

NEC 310.16 Ampacity & Chapter 9 Table 8 Resistance Reference

Size (AWG / kcmil) Cu Ampacity (75°C) Al Ampacity (75°C) Cu Resistance (Ω/1k ft) Al Resistance (Ω/1k ft)

How to Use the Wire Sizer & Voltage Drop Calculator

  1. Select your system voltage — choose from common solar voltages including 12V, 24V, 48V DC, or AC options like 120V, 240V single-phase, and 208V or 480V three-phase systems.
  2. Enter the load current in amps — this is the maximum continuous current your conductor will carry. For solar inverter output circuits, use the inverter's rated output current multiplied by 1.25 per NEC 690.8.
  3. Set the one-way conductor run length — measure the distance from the source (panel, inverter, or combiner box) to the load or connection point in feet. The calculator automatically accounts for the round-trip distance.
  4. Choose conductor material and phase type — select copper or aluminum and single-phase/DC or three-phase AC. The calculator uses the correct resistance values and voltage drop multiplier for your selection.
  5. Review the recommendation — the calculator displays the optimal AWG wire size, actual voltage drop percentage, voltage at the load, and the conductor's 75°C ampacity rating from NEC Table 310.16.

Why Wire Sizing and Voltage Drop Matter for Solar Installers

Proper conductor sizing is one of the most critical aspects of any solar PV installation. NEC Table 310.16 establishes the maximum allowable ampacity for conductors based on their size, insulation temperature rating, and material. Undersized conductors overheat, damage insulation, and create fire hazards — which is why the NEC treats ampacity as a hard limit, not a suggestion.

Voltage drop, while not a code violation in most cases, directly impacts system performance and customer satisfaction. NEC 210.19(A) Informational Note No. 4 recommends limiting branch circuit voltage drop to 3% and total circuit voltage drop (feeder plus branch) to 5%. For solar installations, excessive voltage drop on the DC side means energy produced by the panels never reaches the inverter — effectively reducing system output and extending the customer's payback period.

The voltage drop formula VD = (2 × L × I × R) / 1000 for single-phase and DC circuits (or 1.732 × L × I × R / 1000 for three-phase) uses the conductor's DC resistance per NEC Chapter 9 Table 8. This calculator cross-references both the ampacity requirement and the voltage drop limit to recommend the smallest conductor that satisfies both constraints — saving material cost without compromising safety or performance.

Worked Example: Residential Solar in New Jersey

A solar installer in New Jersey is designing a 7.6 kW residential system with a SolarEdge SE7600H inverter. The inverter's maximum AC output current is 32 amps at 240V single-phase. The run from the inverter to the main service panel is 85 feet one-way through the attic and down an interior wall.

Inputs: System voltage = 240V, load current = 32A, one-way distance = 85 ft, conductor material = copper, phase = single-phase, voltage drop limit = 3%.

Calculation: Starting with AWG 10 (35A ampacity, 1.21 Ω/1000ft): VD = (2 × 85 × 32 × 1.21) / 1000 = 6.58V → 2.74%. This passes the 3% threshold but the 35A ampacity is too close to the 32A load (NEC requires 125% continuous = 40A minimum). Moving to AWG 8 (50A ampacity, 0.778 Ω/1000ft): VD = (2 × 85 × 32 × 0.778) / 1000 = 4.23V → 1.76%.

Result: AWG 8 copper conductor — 50A ampacity (meets 40A continuous requirement), 1.76% voltage drop (well under 3% limit), voltage at panel = 235.8V. The installer can confidently specify 8 AWG THHN copper in the permit drawings.

Frequently Asked Questions

When should I use the 2% voltage drop threshold instead of 3%?

Use 2% for solar DC string wiring and feeder circuits where efficiency is critical. NEC 210.19(A) Informational Note recommends 3% maximum for branch circuits and 5% total for combined feeder plus branch. For solar PV, keeping DC-side voltage drop under 2% maximizes energy harvest since every volt lost in the conductor is energy you paid for panels to produce but never reaches the inverter.

Should I use copper or aluminum conductors for solar installations?

Copper is standard for most residential solar installations due to higher ampacity per size, better corrosion resistance, and easier termination. Aluminum is cost-effective for larger commercial feeders (4/0 AWG and above) where the weight and cost savings outweigh the need for larger conduit. Always use anti-oxidant compound on aluminum terminations and ensure connectors are rated AL/CU.

How does conductor run length affect wire sizing for solar systems?

Longer conductor runs increase resistance losses proportionally. The voltage drop formula VD = (2 × L × I × R) / 1000 shows that doubling the one-way distance doubles the voltage drop. For rooftop solar, runs from the array to the inverter or main panel can easily exceed 100 feet, often requiring you to upsize the conductor beyond the minimum ampacity requirement to stay within voltage drop limits.

Related Free Solar Tools

Ready to Scale Your Solar Business?

Stop calculating manually. Automate wire sizing, permit generation, and compliance checks in one platform.

Automate your full permit pipeline with Solaricy